three-phase (IP55)

FCS3*00
three-phase (IP55)
  • General characteristics

    The three-phase series rated IP55 for outside installation, are controlled by a 0 to 10 Vdc analogue signal from advanced controllers such as FCM, pCO sistema controllers or by a PWM signal (Pulse Width Modulation) from the µchiller series.The range is able to control motors with current ratings from 6 to 40 A, features a control board that distributes the power to the load, in linear or quadratic mode, with the cut off, threshold, and minimum and maximum speed functions set using the trimmers on the board.

    The IP20 range, suitable for panel installation, can be controlled by a 0 to 10 Vdc analogue signal from advanced controllers such as the FCM, pCO sistema controllers or a PWM signal (Pulse Width Modulation) from the µchiller series.These controllers can manage motors with current rating from 9 to 40 A, and feature a control board that distributes the power to the load, in linear or quadratic mode, with the cut off, threshold, and minimum and maximum speed functions set using the trimmers on the board.